Published: September 7, 2026 - 6:01 PM
NICH Fire Safety Audit Exposes Major Hazards, Fourth to Sixth Floors Declared Highly Vulnerable
این آئی سی ایچ فائر سیفٹی آڈٹ میں سنگین خامیاں بے نقاب، چوتھی سے چھٹی منزل انتہائی خطرناک قرار
▫️Faulty fire alarms, defective smoke detectors, oxygen-line leaks and exposed electrical wiring found at Karachi’s major children’s hospital
Karachi | ReNews PakistanSerious fire safety deficiencies have been identified at the National Institute of Child Health (NICH), Karachi, with the hospital’s fourth, fifth and sixth floors declared highly vulnerable to fire hazards follo...
Serious fire safety deficiencies have been identified at the National Institute of Child Health (NICH), Karachi, with the hospital’s fourth, fifth and sixth floors declared highly vulnerable to fire hazards following a detailed safety audit.
The findings were highlighted in a fire safety audit conducted by the Assistant Commissioner of Saddar Sub-Division, which identified critical shortcomings in electrical, oxygen, ventilation, fire detection and emergency evacuation systems across different sections of the hospital, including the Neonatal Intensive Care Unit (NICU).
The audit raised particular concern over the arrangement of electrical and oxygen points inside the NICU, where the two systems have reportedly been installed extremely close to each other, creating a potentially dangerous fire and explosion risk.
The inspection also detected leakage in the oxygen supply line. According to the report, tape had been used as a temporary measure to seal joints in the oxygen pipeline, raising serious questions about the condition and maintenance of the hospital’s oxygen infrastructure.
Unsafe and exposed electrical wiring was also observed at various locations. The report further noted that temporary wiring had been installed for old air-conditioning units, leaving electrical connections exposed and increasing the risk of short circuits and fire.
The NICU’s mechanical ventilation system was found to be non-functional, adding another major concern in an area where critically ill newborns and infants require controlled and safe environmental conditions.
The hospital’s fire detection and warning systems were also found to be in poor condition. The audit reported that the fire alarm system was not functioning, while most of the smoke detectors installed at the facility were also out of order.
The availability of firefighting equipment was found to be inadequate, with the number of fire extinguishers at NICH considered insufficient to provide an effective first response in the event of a fire.
The audit also highlighted serious shortcomings in staff preparedness. Hospital employees had reportedly not received adequate training in fire emergency response, while regular fire drills were not being conducted. The lack of preparedness could significantly delay evacuation and emergency response during an actual fire.
Emergency evacuation routes were another major concern. The inspection found that emergency exits had been blocked by equipment and waste, potentially preventing patients, attendants and hospital staff from escaping quickly in an emergency.
The report also raised concerns over unrestricted public access to the hospital’s power room. According to the audit, the area lacked adequate firefighting arrangements and smoke detection equipment, creating an additional risk around critical electrical infrastructure.
The inspection findings have assumed greater significance in light of previous fire incidents at the hospital. The audit referred to a fire that broke out in the ICU on June 30. It also cited a January 2020 incident in which a newborn died after a fire erupted in an incubator.
Despite these incidents, the report noted that comprehensive fire safety arrangements had yet to be fully implemented across the hospital.
The audit recommended immediate corrective measures to eliminate hazards associated with electrical and oxygen systems, repair the ventilation infrastructure and restore the fire alarm and smoke detection systems.
It also called for all emergency exits to be cleared immediately, adequate fire extinguishers to be installed and regular fire safety drills to be conducted to ensure that hospital staff can respond effectively during emergencies.
The report stressed that comprehensive and effective fire safety arrangements must be implemented across NICH without further delay, particularly in areas such as the NICU where vulnerable newborns and critically ill children require immediate protection and rapid evacuation in case of fire.